10kV、20kV,SBH15-M 型
                              油浸式非晶合金变压器
                              Oil-immersed amorphous alloy transformer

          SBH15-M 型 6~10kV、20kV 油浸式非晶合金铁芯配电变压器技术参数
          Technical parameters of oil-immersed amorphous alloy iron core distribution transformer
           额定容量             电压组合 Voltage combination     联结组标号       空载损耗       负载损耗        空载电流       短路阻抗
           Rated        高压       高压分接范围         低压      Vector Group  No-load   Load loss   No-load   Short circuit
           capacity  high pressure  High pressure   Low pressure   Symbol  loss   (W)       current   impedance
           (kVA)         (kV)   tapping range(%)  (kV)                 (W)                   (%)         (%)
           30                                                          33       630/600      1.70        4.0
           50                                                          43       910/870      1.30        4.0
           63                                                          50      1090/1040     1.20        4.0
           80                                                          60      1310/1250     1.10        4.0
           100                                                         75      1580/1500     1.00        4.0
           125                                                         85      1890/1800     0.90        4.0
           160                                                         100     2310/2200     0.70        4.0
                          6
           200           6.3                                           120     2730/2600     0.70        4.0
           250           6.6        ±5%                   Dyn11        140     3200/3050     0.70        4.0
           315           10       ±2×2.5%        0.4       Yyn0        170     3830/3650     0.50        4.0
           400          10.5                                           200     4520/4300     0.50        4.0
           500           11                                            240     5410/5150     0.50        4.0
           630                                                         320       6200        0.30        4.5
           800                                                         380       7500        0.30        4.5
           1000                                                        450       10300       0.20        4.5
           1250                                                        530       12000       0.20        4.5
           1600                                                        630       14500       0.20        4.5
           2000                                                        750       17400       0.20        5.0
           2500                                                        900       20200       0.20        5.0
          注:当铁芯为三相三柱时,根据需要也可需采用 Yy110 联结组。
          Note: If the core is 3-phase 3-pole, vector group Yyn0 can be used according to requirements.

          SBH15-M 型 6~10kV、20kV 油浸式非晶合金铁芯配电变压器技术参数
          Technical parameters of oil-immersed amorphous alloy iron core distribution transformer

           额定容量             电压组合 Voltage combination     联结组标号       空载损耗       负载损耗        空载电流       短路阻抗
           Rated        高压       高压分接范围         低压      Vector Group  No-load   Load loss   No-load   Short circuit
           capacity  high pressure  High pressure  Low pressure   Symbol  loss    (W)       current   impedance
           (kVA)         (kV)    tap range (% )  (kV)                  (W)                   (%)         (%)
           30                                                          40       690/660      1.50        5.5
           50                                                          55       1010/960     1.20        5.5
           63                                                          65      1200/1150     1.10        5.5
           80                                                          75      1440/1370     1.00        5.5
           100                                                         90      1730/1650     0.90        5.5
           125                                                         100     2080/1980     0.80        5.5
           160                                                         120     2540/2420     0.60        5.5
           200                                                         145     3000/2860     0.60        5.5
           250           24         ±5%                   Dyn11        165     3520/3350     0.60        5.5
           315           22       ±2×2.5%        0.4       Yyn0        200     4210/4010     0.50        5.5
           400           20                                            240     4970/4730     0.50        5.5
           500                                                         290     5940/5660     0.50        5.5
           630                                                         370       6820        0.30        6.0
           800                                                         450       8250        0.30        6.0
           1000                                                        530       11330       0.30        6.0
           1250                                                        620       13200       0.20        6.0
           1600                                                        750       15950       0.20        6.0
           2000                                                        900       19140       0.20        6.0
           2500                                                       1080       22220       0.20        6.0
          注 1: 当铁芯为三相三柱时,根据需要也可采用 Yyn0 联结组。
              2: 对于额定容量为 500kV 及以下的变压器,表中斜线上方的负载损耗值适用于 Dyn11 联结组,斜线下方的负载损耗值适用于 Yyn0 链接组。
              3: 如果用户需要,也可选用其它损耗值。
              4: 根据用户需要,可提供其它高压分接范围的变压器。
          Note 1: If the core is 3-phase 3-poleI vector group Yyn0 can be used according to requirements.
                   2: Rated capacity 500KVA and below transformer, the load loss above the oblique line in the table applies to Dyn11 or Yzn11; the load lossbelow the oblique line applies to Yyn0.
                   3: According to requirements, other loss values can be provided.
                   4: According to requirements, other tap change can be provided.

                                                                                             关注清畅、共创辉煌       54