Page 57 - 清畅电力设备有限公司
P. 57

10KV、20KV,S11/S13
                              油浸式配电变压器
                              Oil-immersed distribution transformers

          S13-M 型 6~10kV 油浸式配电变压器技术参数
          Oil immersed distribution transformer technical parameters
                               电压组合及分接范围
           额定容量           Voltage combinationand tap range  联结组标号    空载损耗       负载损耗        空载电流       短路阻抗
           Rated                                        Vector group   No-load  Load loss   No-load   Short circuit
           capacity     高压       高压分接范围         低压        symbol       loss       (W)       current   impedance
           (kVA)     High pressure  High pressure   Low pressure       (W)                   (%)         (%)
                         (kV)   tapping range(%)  (kV)
           30                                                          80       630/600      1.8         4
           50                                                          100      910/870      1.6         4
           63                                                          110     1090/1040     1.6         4
           80                                                          130     1310/1250     1.5         4
           100                                                         150     1580/1500     1.4         4
           125                                            Dyn11        170     1890/1800     1.4         4
           160            6                               Yzn11        200     2310/2200     1.3         4
           200           6.3                               Yyn0        240     2730/2600     1.2         4
                         6.6         ±5
           250           10       ±2×2.5%        0.4                   290     3200/3050     1.2         4
           315          10.5                                           340     3830/3650     1.1         4
           400           11                                            410     4520/4300     1.1         4
           500                                                         480     5410/5150     1.0         4
           630                                                         570       6200        0.9         4.5
           800                                                         700       7500        0.8         4.5
           1000                                           Dyn11        830       10300       0.8         4.5
           1250                                            Yyn0        970       12000       0.7         4.5
           1600                                                       1170       14500       0.6         4.5


          S13-M 型 20kV 油浸式配电变压器技术参数
          Oil immersed distribution transformer technical parameters

                               电压组合及分接范围
           额定容量           Voltage combinationand tap range  联结组标号    空载损耗       负载损耗        空载电流       短路阻抗
           Rated                                        Vector group   No-load  Load loss   No-load   Short circuit
           capacity     高压       高压分接范围         低压        symbol       loss       (W)       current   impedance
           (kVA)     High pressure  High pressure  Low pressure        (W)                   (%)         (%)
                         (kV)    tap range (% )  (kV)
           50                                                          170     1270/1210     2.00        6.5
           100                                                         230     2120/2020     1.80        6.5
           125                                                         270     2500/2380     1.70        6.5
           160                                                         290     2970/2830     1.60        6.5
           200                                                         340     3500/3330     1.50        6.5
           250                                                         410     4160/3960     1.40        6.5
           315           20          ±5                   Dyn11        490     5010/4770     1.40        6.5
                         22                      0.4
           400           24       ±2×2.5%                  Yyn0        580     6050/5760     1.30        6.5
           500                                                         690     7280/6930     1.20        6.5
           630                                                         830       8280        1.10        6.5
           800                                                         980       9900        1.00        6.5
           1000                                                       1150       12150       1.00        6.5
           1250                                                       1410       14670       0.90        6.5
           1600                                                       1700       17550       0.80        6.5
          注:1、表中斜线上方的负载损耗适用于 Dyn11 联接组,斜线下方的负载损耗值适用于 Yyn0 联接组。
                 2、其它容量的产品性能参数,由用户与制造厂协商确定。
          Note:1. slash the top of the table load loss applicable to Dyn11 join groups, load loss slash Yyn0 below values apply to join the group.
                   2. other capacity product performance parameters, determined by the user in consultation with the manufacturer.

                                                                                             关注清畅、共创辉煌       48