Page 6 - 广东四会互感器厂有限公司
P. 6
㓪ࠊ䇈ᯢ ѻક䗝⫼ݠ
3.7 ⍋ᢨ催ᑺ 1000m ঞҹϟѻકⱘ乱ᅮ㒱㓬∈ᑇ 3.7 The rated insulation level for products applied on
altitude up to 1000m
乱ᅮ⬉य़ ᳔催Ꮉ⬉य़ 乱ᅮ㒱㓬∈ᑇ Rated Highest service Rated insulation
˄kV˅ ˄kV˅ ˄kV˅ voltage(kV) voltage(kV) level(kV)
3 3.6 3.6/25/40 3 3.6 3.6/25/40
6 7.2 7.2/32/60 6 7.2 7.2/32/60
10 12 12/42/75 10 12 12/42/75
15 17.5 17.5/55/105 15 17.5 17.5/55/105
20 24 24/65/125 20 24 24/65/125
35 40.5 40.5/95/185 35 40.5 40.5/95/185
4 ⊼ᛣџ乍 4 Notes
4.1 ⬉⌕Ѧᛳ఼ⱘϔ㒩㒘᳝⬉⌕䗮䖛ᯊˈѠ㒩 4.1 The secondary winding of a current transformer
㒘ϡᕫᓔ䏃DŽ৺߭ᇚ᳝催⬉य़ѻ⫳ˈᇍҎ䑿ᅝܼѻ has not to be open absolutely while primary current is
કᗻ㛑᳝ॅ䰽ᕅડDŽ running in the primary winding. Otherwise there will
produce high voltage. It would be dangerous to personal
safety or affect the performance of productsˊ
4.2 ⬉य़Ѧᛳ఼Ѡ㒩㒘ϡᕫⷁ䏃ˈ৺߭Ѧᛳ఼ᇚ 4.2 There should be no short circuit at the secondary
㹿⚻↕DŽ winding for a voltage transformer, or the voltage
transformer would be damagedˊ
4.3 䞡Ꮉ乥㗤य़䆩偠ˈᑨ㾘ᅮ䆩偠⬉य़ؐⱘ 4.3 The testing voltage has to be 80% stipulated
80%ϟ䖯㸠DŽ testing voltage while repeated power frequency voltage
withstand test neededˊ